Skip to Content
Representative photo. Please check item description for details.

E3 I/O Series, Module-10 RTD Inputs

https://www.branom.com/web/image/product.template/179253/image_1920?unique=c26756c
(0 review)

Red Lion's rugged E3 I/O™ Ethernet-enabled I/O module platform provides powerful networking and reliable remote monitoring and control capabilities for harsh industrial environments. With all-metal housing, wide environmental specifications and industry certifications, our suite of 17 E3 I/O modules offer up to 34 mixed I/O points to meet varying requirements.

Features

Analog Input Channels

  • RTD input range: -200-850 deg C
  • RTD overall accuracy: .05% or .5 deg C
  • A/D resolution 16 bits (0.003%)
  • Temperature coefficient +/- 50 ppm per °C (span and offset)
  • RTD Type: 100 Ohm Platinum
  • RTD Alpha: .00385 or .00392
  • RTD Connections: 2 or 3-wire
  • Scan time: 550 ms for all 10 channels
  • Max lead wire resistance: 100 Ohms per side balanced
  • RTD excitation current:  250uA pulsed to reduce self-heating

Serial Ports 

RS-485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, isolated)  Isolations voltage, 150V  RS-485 networking, Up to 32 (full-load) stations  RS-485 distance, Up to 0.5 miles (baud rate dependent)  Baud Rates from 150 to 57,600 baud  Protocols: master and slave: Sixnet® and Modbus RTU / ASCII  Diagnostic LEDs: Transmit (TD) and Receive (RD) 

Environmental

  • Operating temperature: -40 to 75°C 
  • MTBF: 1,294,803 Hours GB @ 40°C per MIL-HNDBK-217F2

Configuration

  • Configured using Crimson® 3.x software
  • Graphical User Interface (GUI)

1,079.00 1079.0 USD 1,079.00

1,079.00

Not Available For Sale

    This combination does not exist.


    Product Datasheets

    Datasheet 1

    Red Lion's rugged E3 I/O™ Ethernet-enabled I/O module platform provides powerful networking and reliable remote monitoring and control capabilities for harsh industrial environments. With all-metal housing, wide environmental specifications and industry certifications, our suite of 17 E3 I/O modules offer up to 34 mixed I/O points to meet varying requirements.

    Features

    Analog Input Channels

    • RTD input range: -200-850 deg C
    • RTD overall accuracy: .05% or .5 deg C
    • A/D resolution 16 bits (0.003%)
    • Temperature coefficient +/- 50 ppm per °C (span and offset)
    • RTD Type: 100 Ohm Platinum
    • RTD Alpha: .00385 or .00392
    • RTD Connections: 2 or 3-wire
    • Scan time: 550 ms for all 10 channels
    • Max lead wire resistance: 100 Ohms per side balanced
    • RTD excitation current:  250uA pulsed to reduce self-heating

    Serial Ports 

    RS-485 port, Screw terminals (485+, 485-, GND) (2-wire half-duplex, isolated)  Isolations voltage, 150V  RS-485 networking, Up to 32 (full-load) stations  RS-485 distance, Up to 0.5 miles (baud rate dependent)  Baud Rates from 150 to 57,600 baud  Protocols: master and slave: Sixnet® and Modbus RTU / ASCII  Diagnostic LEDs: Transmit (TD) and Receive (RD) 

    Environmental

    • Operating temperature: -40 to 75°C 
    • MTBF: 1,294,803 Hours GB @ 40°C per MIL-HNDBK-217F2

    Configuration

    • Configured using Crimson® 3.x software
    • Graphical User Interface (GUI)